7... HYPERNET™ ICON BASED PROGRAMMING
USING THE OMP-MODL7-10
Various standard Windows techniques are used to select the
different parameters within the dialog box from text entry and editing
to selection via radio buttons.
ICON NAME
Each icon can have an 8 character name assigned that displays
on the workspace under the icon.
OUTPUT NAME
The output signal can be assigned an 8 character name which
displays above the Output Terminal of the icon. This name is
commonly referenced by icons connected to this Output terminal.
For example, if this Thermocouple icon were connected to one
of a Math icon’s input terminals, the name Tinlet would be
referenced within the Math icon as an Input terminal name.
UNITS
Many of the icons can output their signals with various units such
as Degrees C or F, V or mV, Degrees or Ohms, etc. Radio
buttons are typically used to select one of the Unit types.
SIGNAL TYPE OR RANGE
This Thermocouple icon supports 6 different types of
thermocouple. Similarly, other icons have User configurable
ranges or types.
OTHER PARAMETERS
Most of the icons have additional parameters such as filtering,
equations, data types, etc that are all User programmable.
Figure 7... -11: Thermocouple input icon configuration
dialog box